Close up of a Vancouver multiplex side elevation with a narrow side yard, a residential sprinkler head in the ceiling next to a window assembly, the same wall and ceiling assemblies that carry the code's sound separation rating
Building Code & Construction

ASTC 47: The Sound Rule Between Multiplex Homes

9 min read

Section 9.11 of the BC Building Code requires an apparent sound transmission class of 47 between dwelling units, or an STC 50 assembly built with the flanking details in Article 9.11.1.4. What the numbers mean and which junctions decide them.

Key takeaway

Section 9.11 of the BC Building Code requires that a dwelling unit be separated from every other space in which noise may be generated by a separating assembly and adjoining constructions that together provide an apparent sound transmission class (ASTC) of at least 47, or by a separating assembly rated STC 50 with adjoining constructions conforming to Article 9.11.1.4 (Sentence 9.11.1.1.(1), BC Building Code 2018 Revision 2.01).

STC is a laboratory rating of the assembly alone (ASTM E90, ASTM E413); ASTC is the in-building rating including flanking paths (ASTM E336, or calculated under Articles 5.8.1.4 and 5.8.1.5). A secondary suite in a house has a lower bar under Sentence (2): a prescriptive assembly (150 mm sound-absorbing material in joist spaces, filled stud spaces, resilient channel on one side at 400 or 600 mm on centre, 12.7 mm gypsum board on ceilings and both wall faces), or STC 43, or ASTC 40. Elevator shafts and refuse chutes require STC 55.

Compliance (Article 9.11.1.3) is by measurement or calculation, or by building a Table 9.10.3.1.-A or -B assembly with STC of at least 50 plus flanking construction per Article 9.11.1.4: gypsum board on flanking walls and ceilings must end or be interrupted at the separating assembly (or concrete or block above 200 kg/m² at floors and 300 kg/m² at walls), joists must not run continuously across a separating wall, and Table 9.11.1.4 sets floor treatments by wall type (for example 16 mm hardwood parallel, 15.5 mm OSB or plywood plus finish, or 8 kg/m² for W5, W6, W10, W12 and connected double-stud walls; 19 mm concrete topping or 32 kg/m² for W8 and W9; any finished flooring for unconnected double-stud walls and B1 to B10). BKL Consultants reported that the 2018 BC code adopted these flanking rules from the 2015 National Building Code. Builders should name wall and floor designations on drawings, cut the subfloor at double-stud walls, and consider an ASTM E336 field test; buyers should ask for the wall designation and any test report.

What this covers

  • ASTC 47 requirement between dwelling units
  • STC 50 alternative with Article 9.11.1.4 flanking details
  • difference between STC and ASTC
  • secondary suite in a house: STC 43, ASTC 40 or prescriptive assembly
  • Table 9.11.1.4 floor treatments by wall type
  • gypsum board interrupted at separating assemblies
  • STC 55 at elevator shafts and refuse chutes
  • what builders and buyers should ask for
bc-building-code sound-transmission astc stc party-wall flanking

Section 9.11 of the BC Building Code requires that each home in a multiplex be separated from every other space where noise may be generated by construction that achieves an apparent sound transmission class of at least 47. The alternative is a wall or floor assembly rated STC 50 in the laboratory, built with the flanking details the code spells out in Article 9.11.1.4.

Those two numbers, 47 and 50, decide whether the family in Unit 2 hears the television in Unit 1. They also decide how the walls, floors and floor-to-wall junctions of the building are drawn, and they are the part of a multiplex that a buyer cannot see once the drywall is on.

Two ratings, one wall

A sound transmission class, or STC, is a single number describing how much airborne sound a wall or floor blocks. It is measured in a laboratory on a test specimen of the assembly alone, following ASTM E90, and rated under ASTM E413. A higher number blocks more sound.

An apparent sound transmission class, or ASTC, is the same kind of number measured in the finished building between two rooms. It captures the sound that goes through the wall and the sound that goes around it: along the floor, through the ceiling, across the junction where the party wall meets the subfloor. The code calls those side routes flanking paths. ASTC is measured under ASTM E336 or calculated using the methods in Articles 5.8.1.4 and 5.8.1.5.

A wall tested at STC 50 in the lab can perform well below that in a building where the floor sheathing runs continuously under it. That gap is why the code sets the in-building target three points lower than the lab target: ASTC 47 accounts for the flanking that STC 50 ignores.

Acoustic consultancy BKL wrote when the 2018 BC Building Code came into force that the flanking requirements were carried in from the 2015 National Building Code, so the rule has governed BC multiplex construction for several code cycles. The wording quoted in this post is from the BC Building Code 2018, Revision 2.01, Section 9.11. Confirm the clause against the code edition named on your building permit.

What the code requires, in its own words

Sentence 9.11.1.1.(1): a dwelling unit shall be separated from every other space in a building in which noise may be generated by

  • “a separating assembly and adjoining constructions, which together provide an apparent sound transmission class (ASTC) rating of not less than 47,” or
  • “a separating assembly providing a sound transmission class (STC) rating of not less than 50 and adjoining constructions that conform to Article 9.11.1.4.”

The phrase “every other space in which noise may be generated” is broader than the neighbouring home. It includes a shared mechanical room, a common corridor, a garage below, and a laundry room used by more than one unit.

Sentence (3) adds one higher bar: construction separating a dwelling unit from an elevator shaft or refuse chute needs STC 55. A building with an elevator meets that number on the shaft walls.

The lower bar for a suite inside a house

Sentence 9.11.1.1.(2) sets an easier target where a house contains a secondary suite. There, each dwelling unit needs one of:

  • a prescriptive recipe: joist spaces filled with at least 150 mm of sound-absorbing material, stud spaces filled, resilient channel on one side of the separation at 400 or 600 mm on centre, and gypsum board at least 12.7 mm thick on ceilings and on both sides of walls
  • construction rated STC 43
  • a separating assembly and adjoining constructions that together reach ASTC 40

That is a seven-point discount on the ASTC target and a lot less framing. It applies to a suite in a house. Whether a lock-off suite inside one home of a fourplex qualifies depends on how the code’s definitions apply to your building, so ask your designer to point at the clause rather than assuming the discount.

Three ways to prove compliance

Article 9.11.1.3 gives the routes.

Route one: measure or calculate the ASTC. Test the finished separation in the building under ASTM E336, or have it calculated under the Part 5 methods. This is the only route that directly proves the 47.

Route two: build a listed STC 50 assembly with the flanking details. Choose a wall or floor from Table 9.10.3.1.-A or 9.10.3.1.-B, the same tables that list the fire-resistance ratings, with an STC of at least 50, and build the adjoining construction as Article 9.11.1.4 describes. Do both and the code accepts the separation without a field test.

Route three: for a secondary suite in a house, use the prescriptive recipe in Sentence (2)(a).

Route two is where the details live, and where most of the mistakes happen.

The flanking rules, junction by junction

Article 9.11.1.4 tells the framer what to do where the party wall or floor meets the rest of the structure.

Where a wall meets a separating floor or ceiling. The gypsum board finish on the flanking wall must end or be interrupted where it meets the structure of the separating floor. Continuous drywall across that junction carries sound. Concrete or block heavier than 200 kg per square metre is the other option.

Where a wall or ceiling meets a separating wall. Again the drywall must stop at the separating wall’s structure, or for double-stud walls, at the gap between the two rows of studs. Concrete or block heavier than 300 kg per square metre also passes.

Where a floor meets a separating wall. This is the junction that decides most side-by-side multiplexes. The joists or trusses must not run continuously across the party wall, and the floor must carry a treatment over the subfloor matched to the wall type.

Separating wall type (STC 50 or higher, from Table 9.10.3.1.-A)Minimum floor treatment over the subfloor, both sides of the junction
W5, W6, W10, W12 (staggered studs)Wood strip flooring at least 16 mm thick laid parallel to the wall, or one layer of OSB or plywood at least 15.5 mm thick plus finished flooring, or one added layer plus finished flooring with a combined mass of at least 8 kg/m²
W4, W11 (staggered studs)One layer of OSB or plywood at least 12.5 mm plus hardwood strip flooring at least 19 mm laid parallel, or one added layer plus finished flooring of at least 16 kg/m²
W8, W9 (staggered studs)Concrete or gypsum concrete topping at least 19 mm bonded to the subfloor plus finished flooring, or one added layer plus finished flooring of at least 32 kg/m²
W13, W14, W15 (double stud walls) where the subfloor or other rigid material connects the two rows of studsSame as the first row: 16 mm hardwood parallel, or 15.5 mm OSB or plywood plus finish, or 8 kg/m²
W13, W14, W15 where nothing rigid connects the two rows of studs at the junctionAny finished flooring
B1 to B10Any finished flooring

Source: Table 9.11.1.4, BC Building Code 2018, Revision 2.01.

Read the last two rows together. A double-stud party wall with a real break in the subfloor between the two rows of studs needs no extra floor mass at all. The same wall with plywood running under both rows needs the treatment. The difference is one saw cut during framing, and it is invisible after the flooring goes down.

Why a multiplex is the hard case

A detached house has no separating assemblies. A duplex has one wall. A fourplex on a Vancouver lot has a party wall between each side-by-side pair and a floor between each stacked pair, and every one of those meets every other at a junction. The party wall agreement governs who owns and maintains that wall; Section 9.11 governs what is inside it.

The same assemblies also carry the fire separation, so the acoustic choice and the fire choice are one choice. The tables in Section 9.10 list both ratings for each listed wall, which is why a designer picks a wall designation, W13 for example, rather than an STC number. The sprinkler and window decisions on a tight side yard come out of the same section of the code.

What to ask for

If you are building. Have the drawings name the wall and floor designations from Table 9.10.3.1 and show the junction details from Article 9.11.1.4 on the framing plans as well as in a note. Walk the site before drywall and check three things: the subfloor is cut at double-stud walls, the drywall stops at the separating structure, and joists do not run through the party wall. A field test under ASTM E336 after finishing is the only way to know the number, and it is the only number you can show a buyer.

If you are buying. Ask for the wall designation on the party wall and the floor-ceiling assembly, and ask whether a field sound test was done. A builder who can answer both questions in one sentence built the junctions correctly. The first Burnaby multiplex buyers learned to ask for documents before closing. Add the wall designation and the test report to that list.

If you are adding a suite to a house you plan to keep for years. The prescriptive recipe in Sentence (2)(a) is the cheapest legal separation, and it is worth building to the full ASTC 47 anyway if there is any chance the house becomes part of a multiplex conversion later.


Sources: BC Building Code 2018, Revision 2.01, Division B, Section 9.11 Sound Transmission (Articles 9.11.1.1 to 9.11.1.4 and Table 9.11.1.4), Queen’s Printer free access edition; BKL Consultants, “The 2018 BC Building Code Encourages Better Acoustics in Multi-Family Dwellings”; ASTM E90, E336 and E413 as referenced in the code. All read September 17, 2026.

David Babakaiff, Co-Founder, VanPlex | PlexRank™ | Profit with Multiplex

Frequently asked questions

What sound rating does the BC Building Code require between multiplex units?

Sentence 9.11.1.1.(1) requires a dwelling unit to be separated from every other space in which noise may be generated by a separating assembly and adjoining constructions that together provide an apparent sound transmission class (ASTC) of not less than 47, or by a separating assembly with a sound transmission class (STC) of not less than 50 and adjoining constructions that conform to Article 9.11.1.4.

What is the difference between STC and ASTC?

STC is a laboratory rating of a wall or floor assembly on its own, measured under ASTM E90 and rated under ASTM E413. ASTC is the rating between two rooms in the finished building, measured under ASTM E336 or calculated under Articles 5.8.1.4 or 5.8.1.5, and it includes flanking sound that travels around the assembly through floors, ceilings and junctions. A higher number blocks more sound.

What is the sound requirement for a secondary suite in a house?

Sentence 9.11.1.1.(2) sets a lower bar where a house contains a secondary suite: either a prescriptive assembly (joist spaces filled with at least 150 mm of sound-absorbing material, stud spaces filled, resilient channel on one side at 400 or 600 mm on centre, and 12.7 mm gypsum board on ceilings and both sides of walls), or construction rated STC 43, or a separating assembly and adjoining constructions that together reach ASTC 40.

How does a builder prove compliance without a sound test?

Article 9.11.1.3 allows compliance by building a separating assembly from Table 9.10.3.1.-A or 9.10.3.1.-B with an STC of at least 50, together with flanking assemblies built in accordance with Article 9.11.1.4. That article requires gypsum board on flanking walls and ceilings to end or be interrupted at the separating assembly, sets mass thresholds for concrete or block, requires joists not to run continuously across a separating wall, and specifies floor treatments over the subfloor by wall type in Table 9.11.1.4.

What floor treatment does a double-stud party wall need?

Under Table 9.11.1.4, for wall types W13, W14 and W15 where a continuous subfloor or other rigid material connects the two rows of studs, the flanking floor needs hardwood strip flooring at least 16 mm thick laid parallel to the wall, or one layer of OSB or plywood at least 15.5 mm thick plus finished flooring, or an added layer plus finished flooring of at least 8 kg per square metre. Where nothing rigid connects the two rows of studs at the junction, any finished flooring is acceptable.

What sound rating applies next to an elevator shaft?

Sentence 9.11.1.1.(3) requires construction separating a dwelling unit from an elevator shaft or refuse chute to have a sound transmission class rating of not less than 55. That is higher than the 47 ASTC or 50 STC standard between two dwelling units, because an elevator shaft or chute generates more mechanical noise than a neighbouring home.

Does the sound separation rule apply to a garage or shared laundry room in a multiplex?

Yes. Sentence 9.11.1.1.(1) covers separation from every other space in the building where noise may be generated, which the code interprets broadly to include a shared mechanical room, a common corridor, a garage below a unit, and a laundry room used by more than one unit, not just the neighbouring dwelling unit's living space.

Why is a fourplex a harder sound-separation case than a duplex?

A detached house has no separating assemblies to worry about and a duplex has only one shared wall. A fourplex on a typical Vancouver lot has a party wall between each side-by-side pair of units and a floor between each stacked pair, and every one of those assemblies meets every other at a junction that must be detailed under Article 9.11.1.4, multiplying the number of junctions that can fail if built incorrectly.

Free 12-page guide for Vancouver-area homeowners. Build, sell, hold, or partner — side-by-side comparison of the numbers, timeline, and risk on each path.

Verified phone required. We'll text you the link in 60 seconds.

David Babakaiff

David Babakaiff

Co-Founder, VanPlex | 25+ Years BC Construction

David Babakaiff is Co-Founder of VanPlex with 25+ years scaling BC construction. He led Alair Homes Vancouver to the 2024 HAVAN Award for Best Multiplex Unit in the GVRD. VanPlex’s PlexRank™ algorithm scores residential parcels across BC for multiplex conversion potential under Bill 44.

Want insights like this delivered weekly?

Join 2,500+ property owners getting ROI case studies, market data, and exclusive opportunities.

No spam. Unsubscribe anytime.